The CVM-BD Power Meter is a programable measuring instrument supports RS485 Modbus Protocol communication.
- ESP32 device with 320KB RAM, 4MB Flash and RS485 Adapter
- Recommended devices, with RS485 on board:
- T-CAN485
- KAmodESP32 POW RS485
- any other ESP32 device with RS485 interface
- ESPhome
- HomeAssistant
- esphome should installed on your computer or HASS instance (ESPHome Builder)
Example configuration in lilygo-jk0.yaml
lilygo-jk0.yaml - click here to expand
substitutions:
modbus_contr_addr: "10"
modbus_contr_id: cvm
esphome:
name: esp32-s3
friendly_name: ESP32-S3 ESP Circutor CVM-BD-RED
platformio_options:
build_flags: -DBOARD_HAS_PSRAM
board_build.arduino.memory_type: qio_opi
board_build.f_flash: 80000000L
board_build.flash_mode: qio
esp32:
board: esp32-s3-devkitc-1
framework:
type: arduino
# Enable logging
logger:
level: DEBUG
# level: VERY_VERBOSE
# Enable Home Assistant API
api:
encryption:
key: "<your_generated_key>"
ota:
- platform: esphome
password: "<your_ota_password>"
wifi:
ssid: !secret wifi_ssid
password: !secret wifi_password
power_save_mode: none
# Enable fallback hotspot (captive portal) in case wifi connection fails
ap:
ssid: "esp32-S3 Fallback Hotspot"
password: "<your_hotspot_password>"
captive_portal:
time:
- platform: homeassistant
id: homeassistant_time
uart:
id: mod_uart
tx_pin: GPIO43
rx_pin: GPIO44
baud_rate: 19200
stop_bits: 1
rx_buffer_size: 512
debug:
# direction: BOTH
# dummy_receiver: false
# after:
# delimiter: "\n"
# sequence:
# - lambda: UARTDebug::log_string(direction, bytes);
# - lambda: UARTDebug::log_hex(direction, bytes);
modbus:
flow_control_pin: GPIO9
id: modbus1
uart_id: mod_uart
modbus_controller:
- id: ${modbus_contr_id}
address: ${modbus_contr_addr}
modbus_id: modbus1
setup_priority: -10
update_interval: 1s
command_throttle: 75ms
sensor: !include ./include/cvm-bd.yaml
text_sensor: !include ./include/cvm-bd-t.yaml