Skip to content
New issue

Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.

By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.

Already on GitHub? Sign in to your account

Implement default tolerance values #37

Open
lymereJ opened this issue May 7, 2024 · 0 comments
Open

Implement default tolerance values #37

lymereJ opened this issue May 7, 2024 · 0 comments

Comments

@lymereJ
Copy link
Collaborator

lymereJ commented May 7, 2024

@kimw821 developed the following default tolerance values. These should be implemented as default and overridden by users.

Point Label Value Reference
Temperature sensor tolerance 1.0 deg. F Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 2.2
Low supply fan threshold 20.0 % Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 2.2
Minimum MAT threshold 50.0 deg. F Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 2.2
Maximum MAT threshold 90.0 deg. F Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 2.2
Minimum OAT threshold 30.0 deg. F Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 3.3
Maximum OAT threshold 100.0 deg. F Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 3.3
Maximum RAT threshold 90.0 deg. F Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 3.3
Temperature difference tolerance 4.0 deg. F Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 3.3
Maximum damper position 100.0 % Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 3.3
Minimum damper position 10.0 % Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 3.3
OAF temperature tolerance 4.0 deg. F Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 3.3
Cooling enabled tolerance 5.0 deg. F Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 3.3
Desired OAF 10.0 % Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 3.3
Economizer high limit temperature RAT + 1.0 deg. F (DDB Economizer) ASHRAE Guideline 36-2021, High-Performance Sequences of Operation for HVAC Systems
Return air damper tolerance 5.0 % Engineering judgment
Maximum cooling SA temperature 75 deg. F Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 2.2
Minimum cooling SA temperature 50 deg. F Automatic Identification of Retro-commissioning Measures, PNNL-27338, Section 2.2
SA temperature tolerance 6.5 deg. F ASHRAE Guideline 36-2021, High-Performance Sequences of Operation for HVAC Systems
Economizer type Differential Dry-bulb (DDB) Engineering judgment