Skip to content

Latest commit

 

History

History
144 lines (127 loc) · 6.18 KB

enhanced_proto.md

File metadata and controls

144 lines (127 loc) · 6.18 KB

Transfer speed

In order to compensate potential overhead of transfer encoding, the transfer speed is set to 115200 Baud (or 9600 Baud) with 8 bits, no parity, and 1 stop bit.

Protocol

Data bytes with a value below 0x80 can be transferred as is.

Data bytes with value above or equal to 0x80 are split up into two bytes, each one with the highest bit set to 1. The second bit indicates whether it is the first or second byte of a split transfer. This way protocol errors can easily be detected. The bits in the two bytes look like this:

first    second
76543210 76543210
11ccccdd 10dddddd

4 bits in c are used for indicating a special purpose and is set to one of the command request/response symbols as stated below.
8 bits in d are the data byte to be transferred (might also be unused).

Command request/response symbols

from ebusd to interface

  • initialization request
    <INIT> <features>
    Requests an initialization of the interface and optionally requests special features.
    The data byte d indicates interest in certain features (like full message sending instead of arbitration only). The feature bits are defined below in the symbols section.
  • send data request
    <SEND> <data>
    Requests the specified data byte in d to be sent to the eBUS.
    For data byte values <0x80, the short form without the <SEND> prefix is allowed as well.
  • arbitration start request
    <START> <master>
    Requests the start of the arbitration process after the next received <SYN> symbol with the specified master address in d. If the master address is <SYN>, the current arbitration is supposed to be cancelled.
  • information request
    <INFO> <info_id>
    Requests the transfer of additional info identified by info_id. The possible info_id values are defined below in the symbols section. Sending a new info request while the response for the previous one is still in progress immediately terminates the transfer of the previous response.

from interface to ebusd

  • initialization response
    <RESETTED> <features>
    Indicates a reboot or an initial ebusd connection on the interface and is expected to be returned after an <INIT> request.
    The data byte d indicates availability of certain features (like full message sending instead of arbitration only). The feature bits are defined below in the symbols section.
  • receive data notification
    <RECEIVED> <data>
    Indicates that the specified data byte in d was received from the eBUS.
    For data byte values <0x80, the short form without the <RECEIVED> prefix is allowed as well. Note that this message shall not be sent when the byte received was part of an arbitration request initiated by ebusd.
  • arbitration start succeeded <STARTED> <master>
    Indicates the the last arbitration request succeeded (arbitration was won).
    The data byte in d contains the master address that was sent to eBUS during arbitration.
  • arbitration start failed
    <FAILED> <master>
    Indicates that the last arbitration request failed (arbitration was lost or sending failed).
    The data byte in d contains the master address that has won the arbitration.
  • information response
    <INFO> <data>
    Transfers one data byte in response to the INFO request. The first byte transferred in response is the number of data bytes to be transferred (excluding the length itself). The format of the data sequence depends on the info_id value from the request. The possible info_id values are defined below in the symbols section.
  • eBUS communication error
    <ERROR_EBUS> <error>
    Indicates an error in the eBUS UART.
    The data byte in d contains the error message.
  • host communication error
    <ERROR_HOST> <error>
    Indicates an error in the host receiver/transmitter.
    The data byte in d contains the error message.

Symbols

These are the predefined symbols as used above.

Bus symbols

  • SYN 0xAA

Command request symbols (from ebusd to interface)

  • INIT 0x0
  • SEND 0x1
  • START 0x2
  • INFO 0x3

Command response symbols (from interface to ebusd)

  • RESETTED 0x0
  • RECEIVED 0x1
  • STARTED 0x2
  • INFO 0x3
  • FAILED 0xa
  • ERROR_EBUS 0xb
  • ERROR_HOST 0xc

Error codes (from interface to ebusd)

  • ERR_FRAMING 0x00: framing error
  • ERR_OVERRUN 0x01: buffer overrun error

Feature bits (both directions)

  • bit 7-2: tbd
  • // planned: bit 1: full message sending (complete sequence instead of single bytes)
  • bit 0: additional infos (version, HW ID, etc.)

Information IDs (both directions)

The first level below is the info_id value and the second level describes the response data byte sequence. The first byte transferred in response is always the number of data bytes to be transferred (excluding the length itself).

  • 0x00: version
    • length: =8 (2 before 20220220, 5 before 20220831)
    • version: version number
    • features: feature bits (see above)
    • checksum_H checksum_L: checksum (since 20220220)
    • jumpers: jumper settings (0x01=enhanced, 0x02=high speed, 0x04=Ethernet, 0x08=WIFI, 0x10=v3.1, 0x20=ignore hard jumpers)
    • bootloader_version: bootloader version (since 20220831)
    • bootloader_checksum_H bootloader_checksum_L: bootloader checksum
  • 0x01: HW ID
    • length: =9
    • 9*hwid: hardware identifier
  • 0x02: HW config
    • length: =8
    • config_H config_L: hardware config (chip specific)
  • 0x03: HW temperature
    • length: =2
    • temp_H temp_L: hardware temperature in degrees Celsius
  • 0x04: HW supply voltage
    • length: =2
    • millivolt_H millivolt_L: supply voltage in mV, or 0 if unknown
  • 0x05: bus voltage
    • length: =2
    • voltage_max: maximum eBUS voltage in 10th volts, or 0 if unknown
    • voltage_min: minimum eBUS voltage in 10th volts, or 0 if unknown
  • 0x06: reset info (since 20220831)
    • length: =2
    • reset_cause: reset cause (1=power-on, 2=brown-out, 3=watchdog, 4=clear, 5=reset, 6=stack, 7=memory)
    • restart_count: restart count (within same power cycle)
  • 0x07: WIFI status (since 20231226)
    • length: =2